Exam domains and objectives covered
Domain 3: Security Architecture and Engineering Main domain
- 3.8 Apply security principles to site and facility design
- 3.9 Design site and facility security controls
Domain 7: Security Operations
- 7.14 Implement and manage physical security
Objectives are numbered as in the official ISC2® CISSP exam outline.
Learning objectives
By the end of this chapter you should be able to:
- Explain why physical security underpins every other control and why life safety always comes first
- Build a secure facility plan using critical path analysis and apply site selection and CPTED principles
- Apply the functional order of controls and classify physical controls as administrative, technical or physical
- Protect wiring closets, server rooms, media and evidence storage and restricted work areas
- Manage power, noise, HVAC, water and fire risks, including detection and suppression choices
- Select perimeter and internal controls, from fences and person traps to locks, alarms and guards
- Measure physical security with key performance indicators
Key topics
- Secure facility plan and critical path analysis
- Technology convergence
- Site selection and CPTED
- Functional order of controls
- Wiring closets and data centres
- Badges, smartcards and proximity devices
- Intrusion detection and alarms
- Media and evidence storage
- Power quality and UPS
- HVAC, humidity and static
- Fire classes, detection and suppression
- Perimeter and internal controls
- Physical security KPIs
Chapter notes
Chapter overview
If an attacker can walk up to your servers, most technical controls stop mattering. Physical security protects the facilities, equipment and, above all, the people that every other control depends on. This chapter moves from planning a secure site to the controls that run it day to day: site and building design, sensitive rooms, utilities and environment, fire, and the perimeter and internal measures that deter, detect and delay intruders.
Key concepts
People first
Protecting human life always takes priority over protecting assets, in design and in emergencies. Facility designs must also comply with health, safety and building regulations. An occupant emergency plan (OEP) covers keeping people safe during and after a physical incident; IT recovery belongs to the BCP and DRP (Chapters 3 and 18).
Planning a secure facility
- A secure facility plan sets out what needs protecting and how. It comes from risk assessment and critical path analysis, which maps every mission-critical process to the people, technology, utilities and space it depends on (power, HVAC, water, connectivity).
- Technology convergence merges systems such as voice, video, building management and data onto shared infrastructure. It saves money but can create a single point of failure and a more attractive target.
- Security staff should be involved in facility design from the start, and protection should be layered so that intruders face controls in series, one after another, rather than a single barrier.
Site selection and facility design
Security requirements should outrank cost, size and convenience. Assess:
- visibility: should the site stand out or blend in? Industrial camouflage disguises a facility’s real purpose;
- surroundings: neighbouring businesses, crime levels, hazards, noise and vibration, and how close emergency services are;
- accessibility: roads and transport, traffic, entrances (fewer is easier to secure, more is better for evacuation);
- natural and construction risks: local weather, flooding, building materials, fire ratings, load ratings and anything that could hide a break-in.
Crime Prevention Through Environmental Design (CPTED)
CPTED shapes the built environment to discourage crime and reduce fear of crime. It complements, but never replaces, hard controls such as locks and guards.
| Generation | Principles | Idea |
|---|---|---|
| First | Natural access control, natural surveillance, territorial reinforcement, image and milieu | Physical layout: guide people through obvious entrances, keep sight lines open, show the space is owned and cared for |
| Second | Social cohesion, community culture, connectivity, threshold capacity | Social factors: communities that know each other and look out for one another |
Typical CPTED measures: low planters and landscaping that can’t hide people or act as steps, clear and well-lit entrances, few entry points, seating that encourages people to linger and watch, visible cameras, data centres at the core of the building, and delivery entrances kept out of public view.
Classifying physical controls and their functional order
| Type | Examples |
|---|---|
| Administrative | Site selection, building design, personnel procedures, training, emergency procedures |
| Technical | Access control systems, intrusion detection, alarms, cameras, HVAC, fire detection and suppression |
| Physical | Fences, lighting, locks, construction materials, person traps, dogs, guards |
Controls should work in a functional order: deter → deny → detect → delay → determine → decide. Discourage the attempt; block access if that fails; notice the intrusion; slow the intruder long enough for a response; assess what is happening; then choose the response (for example detain the intruder or gather evidence). A cable lock on a laptop is a simple delay control.
Equipment failure
Plan for hardware failure with spares on site, vendor SLAs for replacement times, or both; faster recovery costs more. Lifecycle metrics guide replacement:
- MTTF (mean time to failure): expected working life; replace before it is reached.
- MTTR (mean time to repair): average time to fix a device.
- MTBF (mean time between failures): expected interval between successive failures of a repairable device.
Wiring closets and cable plant
The cable plant runs from the entrance facility (demarcation point where the provider’s cable arrives) through the equipment room, backbone distribution and wiring closets (also called IDFs or telecommunications rooms) to horizontal cabling serving work areas. Protected distribution systems (PDS) use conduits, sealed joints, inspections and sometimes tamper sensors to protect cabling.
Wiring closet rules: never use it for storage or flammable material, lock it (possibly with biometrics), limit keys to authorised staff, log entry with door sensors and cameras, inspect it regularly, include it in environmental monitoring, and tell building management about the access restrictions.
Server rooms and data centres
Server rooms are usually lights-out spaces designed for equipment rather than people. Place them in the building’s core, not on the ground or top floor or in the basement, and away from water, gas and sewage lines. Data centres may be owned, colocated or provided by a cloud provider, and single- or multi-tenant. Typical protections include fire-rated walls, gas suppression, and layered access control:
- Badges identify people (a “dumb” card is just a printed ID); visitor badges should be distinctive and collected afterwards.
- Smartcards carry a chip (often ISO 7816) and act as “something you have”; pair them with a PIN or biometric. Magnetic stripe cards are easily copied.
- Proximity devices are passive (alter the reader’s field), field-powered (energised by the reader, like RFID) or transponders (self-powered and transmitting).
Intrusion detection and alarms
Physical intrusion detection systems (burglar alarms) detect entry or abnormal activity.
| Detector | Senses |
|---|---|
| Contact device (balanced magnetic switch) | A door or window opening |
| Infrared linear beam | Something crossing a beam |
| Passive infrared (PIR) | Changes in heat |
| Wave pattern (ultrasonic or microwave) | Disturbance in a reflected signal |
| Capacitance | Changes in the electrical field around an object |
| Photoelectric | Changes in light in a dark room |
| Passive audio | Unusual sounds |
| Dual-technology | Two methods combined to cut false alarms |
Alarms either deter (lock further doors), repel (sirens and lights) or notify (silent alerts and recording). By location, a local alarm sounds on site and needs nearby responders; a central station alarm alerts an off-site monitoring company (a proprietary system uses the organisation’s own staff); an auxiliary alarm also calls emergency services. Alarms need backup power and heartbeat line supervision so cutting power or cables raises an alert. Use secondary verification (a second sensor or camera review) because more sensitive detectors produce more false alarms.
Cameras deter when visible and detect when footage is reviewed. Options include PTZ, infrared, motion-triggered recording and analytics such as object detection, facial recognition and gait analysis. Networked cameras are themselves attack targets.
Every access control needs monitoring to catch access abuses: doors propped open, tailgating and piggybacking, and impersonation with someone else’s badge. Keep audit trails of entry time, authentication result and how long doors stayed open, and correlate them with footage.
Media, evidence and work area security
- Media storage: locked cabinets or safes, a media librarian or custodian, check-in/check-out, sanitisation (for example zeroisation) when reusable media is returned, and hash checks. Protect blank and installation media from theft and malware planting.
- Evidence storage: a dedicated system separate from production, offline when not in use with no internet access, all activity logged, every dataset hashed and encrypted, and access limited to security administrators and legal counsel.
- Work areas: grade access by sensitivity with concentric layers of protection, put the most valuable assets at the centre, use full-height walls (cutting through suspended ceilings) between zones of different sensitivity, enforce a clean-desk policy and control visitors with escorts and logs. A SCIF (sensitive compartmented information facility) is the high end: tightly restricted, usually with no recording devices allowed.
Power and noise
| Problem | Brief (seconds or less) | Sustained |
|---|---|---|
| Power lost entirely | Fault | Blackout |
| Voltage too low | Sag | Brownout |
| Voltage too high | Spike | Surge |
An inrush is the jump in current drawn when equipment is first switched on or connected.
Protection rises in levels: surge protectors (cut power on overload), power conditioners (also filter noise), UPS units (battery-backed clean power; double conversion runs constantly through the battery, line interactive switches to battery on failure), building-wide battery systems and finally generators for long outages. Keep UPSs even with a generator to bridge the minutes it takes to start. Problems outside the meter are the supplier’s to fix; inside, they are yours.
Noise (electromagnetic interference and radio-frequency interference from motors, lights, lifts and cabling) disrupts power and communications. Counter it with conditioning, proper grounding, shielded cable and conduits, fibre optics and distance from sources.
Temperature, humidity, static and water
- Keep computer rooms at roughly 15–32 °C and stable, since swings cause expansion damage such as chip creep. Use hot and cold aisles to manage airflow.
- Keep relative humidity at roughly 20–80%: too dry builds static and electrostatic discharge (small discharges can destroy components); too humid causes condensation and corrosion.
- Maintain positive air pressure and good filtration to keep out dust and contaminants. Cables in air-handling plenum spaces must be plenum-rated (low smoke and toxic fumes).
- Keep critical equipment away from water pipes, install water detection under raised floors, know where the shut-off valves are, and assess flood risk around the site.
Fire prevention, detection and suppression
Fire needs fuel, heat and oxygen, sustained by a chemical chain reaction; remove any one and it goes out. Water removes heat, dry powders separate the fuel, CO₂ displaces oxygen, and halon substitutes interrupt the chemical reaction. Fires progress from incipient (ionisation only) to smoke, flame and finally heat; earlier detection means less damage.
| US class | Fuel | Suitable suppressants |
|---|---|---|
| A | Ordinary combustibles (paper, wood) | Water, foam, dry chemical |
| B | Flammable liquids | CO₂, foam (AFFF), dry chemical, clean agents |
| C | Electrical equipment | CO₂, clean agents (never water) |
| D | Combustible metals | Dry powder |
| K | Cooking oils and fats | Wet chemical (alkaline agents) |
The exam uses the US classification. UK and European classes differ: A solids, B flammable liquids, C flammable gases, D metals and F cooking oils, with electrical fires shown by a separate symbol rather than a class.
Detection: fixed-temperature (cheap, reliable, the sprinkler bulb is both sensor and valve), rate-of-rise (can be fooled by heating), flame-actuated (infrared, fast but expensive), smoke (photoelectric or ionisation) and incipient/aspirating detectors that sense the earliest combustion products. Place detectors in ceiling voids, raised floors, ducts and lift shafts too.
Water systems:
- Wet pipe: always charged; discharges immediately. Simple, but a damaged head floods the area.
- Dry pipe: pressurised air or gas holds back water until triggered.
- Pre-action: fills on first detection, discharges only when a sprinkler head also activates; gives time to cancel a false alarm, so it is the best water option where people and computers mix.
- Deluge: every head opens at once with large volumes; unsuitable for IT rooms.
Gas systems (CO₂, halon replacements such as FM-200 and other clean agents) cause the least damage to equipment and act quickly, but many displace oxygen. CO₂ in particular is lethal at extinguishing concentrations, so use it only where people won’t be present. Halon is banned from new production under the Montreal Protocol because it depletes ozone. Remember that smoke, heat, the suppressant and firefighters can all damage equipment, and that people need training, drills and at least two known escape routes.
Perimeter controls
- Fences: roughly 1 m (3–4 ft) deters casual trespassers; about 2 m (6–7 ft) is hard to climb; 2.4 m (8 ft) or more topped with barbed or razor wire deters determined intruders. A PIDAS (perimeter intrusion detection and assessment system) uses multiple fences with sensors and a patrol corridor; the outer fence reduces nuisance alarms from animals.
- Gates must be as strong as the fence; keep them few and monitored. Turnstiles admit one person at a time in one direction.
- Access control vestibules (person traps, mantraps) hold a person between two doors until verified, defeating tailgating and piggybacking; some include weight checks.
- Bollards and barricades stop vehicle attacks; avoid long straight approach roads.
- Lighting is the most common perimeter control but only a weak deterrent. Light critical areas to around 2 foot-candles (about 20 lux), overlap the pools of light, avoid glare that blinds guards or cameras, and combine lighting with surveillance.
- Guards bring judgement and adaptability; patrol at random intervals. Downsides: cost, reliability, susceptibility to social engineering, and limited protection when their own lives are at risk. Guard dogs detect and deter but are costly and raise liability concerns; robot sentries and drones are emerging alternatives.
- Signage warns, deters and supports enforcement; test all physical controls on a schedule.
Internal controls
Use reception as a choke point, escort visitors, keep visitor and access logs (also useful for roll calls in an evacuation) and grade areas as public, private or restricted. Locks range from conventional keyed locks (vulnerable to picking, shimming and bumping) to programmable and electronic access control (EAC) locks combining an electromagnet, a credential reader and a door sensor that can raise an alarm if a door is held open. Add badges, motion detectors, intrusion alarms and cameras inside as well as at the perimeter.
Measuring physical security
Track KPIs against a baseline to show trends and justify spending, for example successful and unsuccessful intrusions, time to detect, assess, respond and recover, impact of incidents and the false alarm rate. Collect extra data during lessons-learned reviews.
Exam tips
- Human safety is always the first answer when lives are at risk.
- Person traps (access control vestibules) defeat tailgating and piggybacking.
- Pre-action sprinklers suit data centres; wet pipe systems risk accidental water damage.
- Degaussing, shredding and other media controls connect this chapter to asset security (Chapter 5).
- Security requirements, not cost, should drive site selection.
- Know the functional order of controls in sequence; questions often ask what comes next.
Common traps
- Sag vs brownout, spike vs surge, fault vs blackout. The first of each pair is momentary; the second is prolonged.
- Never use water on electrical (class C) fires, and don’t use oxygen-removal methods on metal fires.
- Exam fire classes are American. In the UK, class C means gases and cooking oils are class F.
- Lighting is a deterrent, not a strong control. It should never be the only protection.
- Cameras. Visible cameras deter; reviewed recordings detect. A camera nobody watches doesn’t respond to anything.
- Dry pipe ≠ pre-action. Pre-action adds a second trigger, giving time to cancel; dry pipe simply delays water until the pipes fill.
- Gas suppression and people don’t mix. Choose it for unoccupied equipment spaces.
- OEP vs BCP. The OEP protects people and property; it doesn’t cover IT recovery.
Quick revision
- Physical security underpins logical security; life safety comes first.
- Secure facility plan = risk assessment + critical path analysis; watch for convergence creating single points of failure.
- Site selection: visibility, surroundings, accessibility, natural hazards; security over cost.
- CPTED: access control, surveillance, territorial reinforcement, image (first generation); social factors (second generation).
- Order of controls: deter, deny, detect, delay, determine, decide.
- Wiring closets: locked, logged, no storage, inspected; PDS protects cables.
- Data centres: core of building, away from water, lights-out, layered access control.
- Alarms: deterrent, repellent, notification; local, central station, auxiliary; heartbeat and backup power.
- Power: surge protector, conditioner, UPS, generator; know the fault terms.
- Environment: about 15–32 °C, 20–80% humidity, positive pressure, water detection.
- Fire: triangle, four stages, US classes A/B/C/D/K, pre-action for IT, gas for unoccupied spaces.
- Perimeter: fences by height, PIDAS, gates, turnstiles, vestibules, bollards, lighting, guards, dogs.
- Track KPIs against a baseline.
Key terms
| Term | Definition |
|---|---|
| Critical path analysis | Mapping the dependencies that keep mission-critical operations running |
| Technology convergence | Merging separate systems onto shared infrastructure, potentially creating a single point of failure |
| CPTED | Designing buildings and landscapes so the environment itself discourages crime |
| Functional order of controls | Deter, deny, detect, delay, determine, decide |
| Protected distribution system (PDS) | Physical safeguards that protect network cabling from tampering |
| Access control vestibule | Two interlocking doors that hold a person until their access is confirmed |
| PIDAS | A multi-fence perimeter with intrusion sensors and a patrol corridor |
| Heartbeat sensor | Line supervision that raises an alarm if the alarm’s communication path fails |
| UPS | Battery-backed equipment that supplies clean power through short outages |
| Brownout | A prolonged period of low voltage |
| Pre-action system | A sprinkler system needing two triggers before water is released |
| Plenum | Air-handling space where cabling must be rated for low smoke and toxicity |
| SCIF | A highly restricted facility for handling sensitive compartmented information |
| Occupant emergency plan (OEP) | A plan for protecting staff and property during a physical emergency |